Schneider Electric Vigilohm insulation monitoring device. VIGILOHM IM20 - H 110-230 V CA.
VIGILOHM IM20 - H 110-230 V CA. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | Vigilohm |
|---|
| Device short name | IM20-H |
|---|
| Product or component type | Insulation monitoring device |
|---|
| Type of IMD | AC IMD |
|---|
| Earthing system | IT |
|---|
| Application | Group II medical premise · Healthcare |
|---|
| Electrical circuit type | Control circuit |
|---|
| Network capacitance | Lightly capacitive |
|---|
| Type of network | 1P + N |
|---|
| Network rated voltage | 0…230 V - AC at 50/60 Hz (device connected to neutral) · 0…230 V - DC |
|---|
| Alarm threshold setting | Alarm: 50...500 kOhm |
|---|
| Type of measurement | Network insulation resistance, range: 1 kOhm...10 MOhm, accuracy: +/- 5 % · History of alarms |
|---|
| Configurable filtering time | 1 s |
|---|
| Response time | 0.8 s 1/5th of set filtering time · 8 s 1/5th of set filtering time · 32 s 1/5th of set filtering time |
|---|
| Alarm function | IT transformer overheat · IT transformer overload |
|---|
| Self-test | Manual · Auto test |
|---|
| Relative impedance | 141 kOhm at 2.5 Hz |
|---|
| IP degree of protection | Front face: IP52 · Rear: IP20 |
|---|
| Material | Thermoplastic |
|---|
| Type of installation | Indoor |
|---|
| Operating altitude | <= 3000 m |
|---|
| Relative humidity | 0…92 % |
|---|
| Ambient air temperature for operation | -25…55 °C |
|---|
| Ambient air temperature for storage | -40…70 °C |
|---|
| Pollution degree | 2 |
|---|
| Mounting mode | Clip-on (DIN rail) · Flush-mounted (panel) |
|---|
| Connections - terminals | Removable screw terminal block 0.2…2.5 mm² |
|---|
| Product weight | 0.25 kg |
|---|
| Cut-out dimensions | 92.4 x 92.4 mm |
|---|
| Height | 110 mm |
|---|
| Width | 96 mm |
|---|
| Depth | 59 mm |
|---|
| Display type | LCD display |
|---|
| Information displayed | Resistance value · IT transformer alarms · Evolution of resistance in graph |
|---|
| User language | Russian · Spanish · French · Chinese · German · Portuguese · English · Italian |
|---|
| Local signalling | Green indicator light: satisfactory insulation resistance · Orange audible and visible alarms: below fault threshold |
|---|
| Signal contacts composition | 2 C/O standard or fail-safe |
|---|
| Signalling circuit voltage | 12...48 V - DC at 50 mA |
|---|
| Communication port protocol | Modbus RS485 |
|---|
| Communication of data | HMI: test reports · Dry contact: test reports |
|---|
| Fault event log | Alarm logs |
|---|
| Product compatibility | Automatic fault locator |
|---|
| [Us] rated supply voltage | 110...230 V AC 50/60 Hz tolerance: +/- 15 % · 125...250 V DC tolerance: +/- 15 % |
|---|
| Power consumption in VA | 12 VA |
|---|
| Overcurrent protection | 1 A |
|---|