Schneider Electric Vigilohm insulation monitoring device. VIGILOHM IM9 - OL 110-415 V CA.
VIGILOHM IM9 - OL 110-415 V CA. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | Vigilohm |
|---|
| Device short name | IM9-OL |
|---|
| Product or component type | Insulation monitoring device |
|---|
| Type of IMD | AC IMD |
|---|
| Earthing system | TT · TN-S · IT |
|---|
| Application | Off-line application |
|---|
| Electrical circuit type | Offline device |
|---|
| Type of network | 1P + N · 3P · 3P + N |
|---|
| Network rated voltage | 0…690 V - AC at 45...440 Hz (device connected to neutral) |
|---|
| Alarm threshold setting | Pre-alarm: 0.5...10 MOhm · Alarm: 0.25...2 MOhm |
|---|
| Type of measurement | Stator insulation resistance, range: 250 kOhm...10 MOhm, accuracy: +/- 15 % |
|---|
| Configurable filtering time | 2 s |
|---|
| Response time | 2 s 100 % |
|---|
| Self-test | Manual |
|---|
| Overvoltage category | III |
|---|
| IP degree of protection | Case: IP20 · Front face: IP40 |
|---|
| Material | Thermoplastic |
|---|
| Type of installation | Indoor |
|---|
| Operating altitude | <= 3000 m |
|---|
| Relative humidity | 0…92 % |
|---|
| Ambient air temperature for operation | -25…55 °C |
|---|
| Ambient air temperature for storage | -40…70 °C |
|---|
| Pollution degree | 2 |
|---|
| Mounting mode | Clip-on (DIN rail) · Flush-mounted (panel) |
|---|
| Mounting position | Horizontal · Vertical |
|---|
| Connections - terminals | Tunnel type terminals 0.2…2.5 mm² |
|---|
| Product weight | 0.2 kg |
|---|
| Cut-out dimensions | 66 x 72.5 mm |
|---|
| Height | 90 mm |
|---|
| Width | 71 mm |
|---|
| Depth | 67.5 mm |
|---|
| Display type | Without display |
|---|
| Signal contacts composition | 1 C/O standard · 1 C/O fail-safe |
|---|
| Signalling circuit voltage | 250 V - AC at 6 A · 12...24 V - DC at 6 A |
|---|
| Communication port protocol | - |
|---|
| Communication of data | HMI: test reports |
|---|
| [Us] rated supply voltage | 110...415 V AC 50/60/400 Hz tolerance: +/- 15 % · 125...250 V DC tolerance: +/- 15 % |
|---|
| Power consumption in VA | 7 VA |
|---|
| Power consumption in W | 3 W |
|---|
| Overcurrent protection | 1 A |
|---|
| Standards | IEC 61557-8 · UL 61010-1 · IEC 61010-1 · IEC 61326-2-4 |
|---|
| Product certifications | EAC · DNV · CE · RCM · EU-RO MR TA |
|---|
| Environmental characteristic | Exposure to damp heat not in service conforming to IEC 60068-2-30 · Exposure to damp heat in service conforming to IEC 60068-2-56 · Salt mist conforming to IEC 60068-2-52 · Long-term storage class 1K22 conforming to IEC 60721-3-1 · Transport class 2K11 conforming to IEC 60721-3-2 · Stationary use at weather protected locations class 3K24 conforming to IEC 60721-3-3 |
|---|
| Mechanical robustness | Long-term storage class 1M11 conforming to IEC 60721-3-1 · Transport class 2M4 conforming to IEC 60721-3-2 · Stationary use class 3M11 conforming to IEC 60721-3-3 |
|---|
| Unit Type of Package 2 | S03 |
|---|